HomeMy WebLinkAboutORD 1345 (2007)ORDINANCE N0. 1345
AN ORDINANCE OF THE CITY COUNCIL OF THE CITY OF TUSTIN
AMENDING SPECIFIED SECTIONS OF CHAPTER 1 OF ARTICLE 5 OF
THE TUSTIN CITY CODE TO ADOPT THE 2007 CALIFORNIA FIRE
CODE AS AMENDED THERETO
The City Council of the City of Tustin does hereby find and ordain as follows:
Section 1
WHEREAS, Health and Safety Code Section 17958 provides that the City of
Tustin ("City„) shall adopt Ordinances and regulations imposing the same or modified or
changed requirements as are contained in the regulations adopted by the State
pursuant to Health and Safety Code Section 17922; and
WHEREAS, the State of California is mandated by Health and Safety Code
Section 17922 to impose the same requirements as are contained in the txiost recent
edition of the model fire code, the International Fire Code, 2006 Edition, as amended by
the S#ate of California, published by the International Code Council (hereinafter referred
to collectively as "Fire Code"); and
WHEREAS, Health and Safety Code Section 17958.5(a) permits the City to
make modifications or changes to the Codes, which are reasonably necessary because
of local climatic, geographic or topographic conditions; and
WHEREAS, Health and Safety Code Section 17958.7 requires that the City
Council, before making any modifications or changes to the Codes, shall make an
express finding that such changes or modifications are reasonably necessary because
of local climatic, geographic or topographic conditions; and
WHEREAS, the Community Development Department and Orange County Fire
Authority have recommended that changes and modifications be made to the Fire Code
and have advised that certain said changes and modifications to the California Fire
Code, 2007 Edition are reasonably necessary due to local conditions in the City of
Tustin and have further advised that the remainder of said changes and modifications
are of an administrative or procedural nature, or concern themselves with subjects not
covered by the Code or are reasonably necessary to safeguard life and property within
the City of Tustin.
Section 2 Findings
WHEREAS, amendments related to fire safety contained in Chapters 1 through
47, Appendix Chapters 1, Appendix B, C and H, excluding Chapter 4, of the 2006
International Fire Code with errata, recommended by the Community Development
Department and Orange County Fire Authority are reasonably necessary due to the
following local conditions.
Ordinance No. 1345
Page 2
I. Climatic Conditions
A. The City of Tustin is located in a semi-arid Mediterranean type climate. It
annually experiences extended periods of high temperatures with little or no
precipitation. Hot, dry Santa Ana winds, which may reach speeds of 70 m.p.h.
or greater are also common to the area. These climatic conditions cause
extreme drying of vegetation and common building materials. Frequent
periods of drought and low humidity add to the fire danger. This predisposes
the area to large destructive fires (conflagration). In addition to directly
damaging or destroying buildings, these fires also disrupt utility services
throughout the area.
(For High Rise Only) Obstacles generated ~ by strong winds, such as fallen
trees, street lights and utility poles, and the requirement to climb 75 feet
vertically up flights of stairs will greatly impact the response time to reach an
incident scene. Additionally, #here is a significant increase in the amount of
wind force at 60 feet above the ground. Use of aerial type fire fighting
apparatus above this height would place rescue personnel at increased risk of
injury.
B. The climate alternates between extended periods of drought and brief flooding
conditions. Flood conditions may affect the Orange County Fire Authority's
ability to respond to a fire or emergency condition. Floods also disrupt utility
services to buildings and facilities within the County.
C. Water demand in this densely populated area far exceeds the quantity
supplied by natural precipitation; and, although the population continues to
grow, the already-taxed water supply does not. California is projected to
increase in population by nearly 10 million over the next quarter of a century
with 50 percent of that growth centered in Southern California. Due to storage
capacities and consumption and a limited amount of rainfall, future water
allocation is not fully dependable. This necessitates the need for additional
on-site fire protection features. The shortage of water would also leave tall
buildings vulnerable to uncontrolled fires due to a lack of available water and
an inability to pump sufficient quantities of available water to upper floors in a
fire.
D. These dry climatic conditions and winds contribute to the rapid spread of even
small fires originating in high-density housing or vegetation. These fires
spread very quickly and create a need for increased levels of fire protection.
The added protection of fire sprinkler systems and other fire protection
features will supplement normal fire department response by providing
immediate protection for the building occupants and by containing and
controlling the fire spread to the area of origin. Fire sprinkler systems will also
reduce the use of water for firefighting by as much as 50 to 75 percent.
Ordinance No. 1345
Page 3
II. Topographical conditions
A. Natural slopes of 15 percent or greater generally occur throughout the foothills
of Orange County. The elevation change caused by the hills creates the
geological foundation on, which communities within Orange County are built
and will continue to build. With much of the populated flatlands already built
upon, future growth will occur on steeper slopes and greater constraints in
terrain.
B. Traffic and circulation congestion is an artificially created, obstructive
topographical condition, which is common throughout Orange County.
C. These topographical conditions combine to create a situation, which places
fire department response time to fire occurrences at risk, and makes it
necessary to provide automatic on-site fire-extinguishing systems and other
protection measures to protect occupants and property.
III. Geological conditions
The Orange County region is a densely populated area that has buildings constructed
over and near a vast and complex network of faults that are believed to be capable of
producing future earthquakes similar or greater in size than the 1994 Northridge and the
1971 Sylmar earthquakes. Earthquake faults run along the northeast and southwest
boundaries of Orange County. The Newport-Inglewood Fault, located within Orange
County was the source of the destructive 1933 Long Beach earthquake (6.3 magnitude)
which took 120 lives and damaged buildings in an area that ran from Laguna Beach to
Marina del Rey to Whittier. In December 1989, another earthquake occurred in the
Irvine at an unknown fault line. Regional planning for reoccurrence of earthquakes is
recommended by the State of California, Department of Conservation.
A. Previous earthquakes have been accompanied by disruption of traffic flow and
fires. A severe seismic event has the potential to negatively impact any
rescue or fire suppression activities because it is likely to create obstacles
similar to those indicated under the high wind section above. With the
probability of strong aftershocks there exists a need to provide increased
protection for anyone on upper floors of buildings. The October 17, 1989,
Santa Cruz earthquake resulted in one major fire in the Marina District (San
Francisco). When combined with the 34 other fires locally and over 500
responses, the department was taxed to its fullest capabilities. The Marina fire
was difficult to contain because mains supplying water to the district burst
during the earthquake. This situation creates the need for both additional fire
protection and automatic on-site fire protection for building occupants. The
State Department of Conservation noted, in their 1988 report (Planning
Scenario on a Major Earthquake on the Newport Inglewood Fault Zone, page
59}, "unfortunately, barely meeting the minimum earthquake standards of
building codes places a building on the verge of being legally unsafe."
Ordinance No. 1345
Page 4
B. Road circulation features located throughout the County also make
amendments reasonably necessary. There are major roadways, highways
and flood control channels that create barriers and slow response times. Hills,
slopes, street and storm drain design accompanied by occasional heavy
rainfall, cause roadway flooding and landslides and at times may make an
emergency access route impassable. There are areas in Orange County that
naturally have extended emergency response times that exceed the 5 minute
goal.
C. Soils throughout the County posses corrosive properties that reduce the
expected usable life of water services when metallic. pipes come in contact
with these soils.
Due to the topographical conditions of sprawling development separated by waterways
and narrow and congested streets and the expected infrastructure damage inherent in
seismic zone described above, it is prudent to rely on automatic fire sprinkler systems to
mitigate extended fire department response time and keep fires manageable with
reduced fire flow (water) requirements for a given structure. Additional fire protection is
also justified to match the current resources of firefighting equipment and personnel
within the Orange County Fire Authority.
Additional amendments have been made to the California Fire Code, 2007 Edition and
its Appendix. On the recommendation of the Community Development Department,
such amendments are hereby found to be either administrative or procedural in nature
or concern themselves with subjects not covered in the California Fire Code.
Section 3 Ordinance Amendmenfs
Sections 5130.010 through 5130.300 of Chapter 1 Part 3 of Article 5 of the Tustin
City Code are hereby repealed i.n their entirety, and new Sections 5130 and 5131 of
Chapter 1 Part 3 of Article 5 are hereby added in place thereof to read as follows:
5130.01 Adoption of the California Fire Code and the Amended
Uniform Fire Code
5130.02 Enforcement and Inspections Amended
5131.A1 Appendix chapter 1 -Administration Adopted and
amended
5131.01 Chapter 1 -General code provisions Adopted
5131.02 Chapter 2 -Definitions Adopted and
amended
5131.03 Chapter 3 -General precautions against fire Adopted and
amended
Ordinance No. 1345
Page 5
5131.04 Chapter 4 -Emergency planning and
re aredness Not adopted
5131.05 Chapter 5 -Fire service features Adopted and
amended
5131.06 Chapter fi -Building services and systems Adopted and
amended
5131.07 Chapter 7 -Fire-resistance-rated construction Adopted
5131.08 Chapter 8 -Interior finish, decorative materials
and furnishin s Adopted
5131.09 Chapter 9 -Fire protection systems Adopted and
amended
5131.10 Chapter 10 -Means of egress Adopted
5131.1'1 Chapter 11 -Aviation facilities Adopted and
amended
5131.12 Chapter 12 -Dry cleaning Adopted
5131.13 Chapter 13 -Combustible dust-producing
o erations Adopted
5131.14 Chapter 14 -Fire safety during construction and
demolition Adopted
5131.15 Chapter 15 -Flammable finishes Adopted
5131.16 Chapter 16 -Fruit and crop ripening Adopted
5131.17 Chapter 17 -Fumigation and therms! insecticidal
fo in Adopted and
amended
5131.18 Chapter 18 -Semiconductor fabrication facilities Adopted
5131.19 Chapter 19 -Lumber yards and woodworking
facilities Adopted and
amended
5131.20 Chapter 20 -Manufacture of organic coatings Adopted
5131.21 Chapter 21 -Industrial ovens Adopted
5131.22 Chapter 22 -Motor fuel-dispensing facilities and
re air ara es Adopted
5131.23 Chapter 23 - High•piled combustible storage Adopted and
amended
5131.24 Chapter 24 -Tents, canopies and other
membrane structures Adopted
5'131.25 Chapter 25 -Tire rebuilding and tire storage Adopted
Ordinance No. 1345
Page 6
5131.26 Chapter 26 -Welding and other hot work Adopted
5131.27 Chapter 27 -Hazardous materials general
rovisions Adopted and
amended
5131.28 Chapter 28 -Aerosols Adopted
5131.29 Chapter 29 -Combustible fibers Adopted
5131.30 Chapter 30 -Compressed gases Adopted
5131.31 Chapter 31 -Corrosive materials Adopted
5131,32 Chapter 32 -Cryogenic fluids Adopted and
amended
5131.33 Chapter 33 -Explosives and fireworks Adopted and
amended
5131.34 Chapter 34 -Flammable and combustible liquids Adopted and
amended
5131.35 Chapter 35 -Flammable gases Adopted
5131.36 Chapter 36 -Flammable solids Adopted
5131.37 Chapter 37 -Highly toxic and toxic materials, Adopted
5131.38 Chapter 38 - Liquefed petroleum gases Adopted
5131.39 Chapter 39 -Organic peroxides Adopted
5131.40 Chapter 40 -Oxidizers Adopted
5131.41 Chapter 41 - Pyrophoric materials Adopted
5131.42 Chapter 42 -Pyroxylin (cellulose nitrate) plastics Adopted
5131.43 Chapter 43 -Unstable (reactive) materials Adopted
5'131.44 Chapter 44 -Water-reactive solids and liquids Adopted
5131.45 Chapter 45 -Referenced standards Adopted and
amended
5131.46 Chapter 46 -Motion picture and television ~
production studio sound stages, approved
roduction facilities and roduction locations Adopted
5131.47 Chapter 47 -Requirements for wildland-urban
interface areas Adopted and
amended
Ordinance No. 1345
Page 7
5131.A1 Appendix chapter 1 -Administration Adopted and
amended (see
row 3 of this
table
5131.A4 Appendix chapter 4 -Special detailed Not Adopted
re uirements based on use and occu anc
5131.AA Appendix A -Board of appeals Not Adopted
5131.AB Appendix B -Fire-flow requirements for buildings Adopted and
amended
5131.AC Appendix C -Fire hydrant locations and Adopted and
distribution amended
5131.AD Appendix D -Fire apparatus access roads Not Adopted
5131.AE Appendix E -Hazard categories Not Adopted
5131.AF Appendix F -Hazard ranking Not Adopted
5131.AG Appendix G -Cryogenic fluids-weight and volume Not Adopted
e uivalents
5131.AH Appendix H -Hazardous materials management Adopted
plans and hazardous materials inventory
statements
5130.01 Adoption of the California Fire Code
The 2007 California Fire Code, based on the lriternational Fire Code, 2006 Edition with
errata, Including Appendix Chapter 1, Appendices B, C, and H, excluding Chapter 4,
Appendices A, D, E, F, and G, published by the International Code Council, are hereby
adopted by the City of Tustin for the purpose of prescribing regulations governing
conditions hazardous to the life and property from fire or explosion, save and except
such portions as are hereinafter added, deleted, modified or amended. The California
Fire Code will be on file for public examination in the Community Developmen#
Department.
5130.02 Enforcement and Inspections
The California Fire Code and the International Fire Code with amendments shall be
enforced by the Orange County Fire Authority, which shall be operated under the
Director of Fire Services of the Orange County Fire Authority. The Director of Fire
Services of the Fire Authority may detail such members of the Fire Authority as
Inspectors as shall be necessary from time to time.
5131.A1 APPENDIX CHAPTER 1 -ADMINISTRATION of the 2007 California Fire Code
is hereby amended with the following modifications:
Ordinance No. 1345
Page 8
(a) SECTION 102.9; Conflicting Provisions, is hereby deleted and replaced
with the following:
"102.9 Conflicting Provisions. Where there is a conflict between a
general requirement and a specific requirement, the fire code official shall
decide which requirement meets the general intent of this code."
(b) SECTION 105.6, Required Operational Permits is hereby amended by
modifying and deleting permit categories as follows:
"105.5.29. Miscellaneous combustible storage. Permit is required to
store in any building or upon any premise in excess of 2500 cu. ft. gross
volume of combustible empty packing cases, boxes, barrels or similar
containers, rubber tires, rubber, cork, composting, green waste, or similar
combustible material."
(c) Section 105.6.15 Fire hydrants and valves is hereby deleted without
substitution.
(d) Section 105.6.35 Private fire hydrants is hereby deleted without
substitution.
(e) SECTION 109.3, Violation penalties, is hereby amended and by adding
new Sections 109.3.2, Infraction, and 109.3.3, Misdemeanor, as follows:
"109.3 Violation penalties. Persons who shall violate a provision of this
code or shall fail to comply with any of the requirements thereof or who
shall erect, install, alter, repair or do work in violation of the approved
construction documents or directive of the fire code official, or of a permit
or certificate used under provisions of this code, shall be guilty of a
misdemeanor or infraction as prescribed in Section 109.3.2 and 109.3.3.
Penalties shall be as prescribed in local ordinance. Each day that a
violation continues after due notice has been served shall be deemed a
separate offense.
109.3.2 Infraction. Except as provided in Section 109.3.2, persons
operating or maintaining any occupancy, premises or vehicle subject to
this code that shall permit any fire or life safety hazard to exist on
premises under their control shall be guilty of an infraction.
109.3.3 Misdemeanor. Persons who fail to take immediate action to
abate a fire or life safety hazard when ordered or notified to do so by the
chief or a duly authorized representative, or who violate the following
sections of this code, shall be guilty of a misdemeanor:
Ordinance No. 1345
Page 9
103.4.3 Compliance with Orders, Notices and Tags
107.6 Overcrowding
104.11.2 Obstructing operations
104.11.3 Systems and Devices
111.4 Failure to comply
305.4 Deliberate or negligent burning
308.2.1Throwring or placing sources of ignition
310.7 Burning Objects
2404.7 Open or exposed flame"
5131.01 (Reserved)
5131.02 Chapter 2 of the 2007 California Fire Code is hereby amended as follows:
(a) SECTION 202, General Definitions, is hereby amended by adding the
following definitions:
"ALTERATION: Any construction or renovation to an existing structure
other than a repair or addition. Alterations include but are not limited to
the addition or elimination of walls within the existing building envelope.
Alteration also includes modifications to the structure which involve
complete removal and replacement of wall board within any room.
FLOOR AREA, for the purpose of calculating square footage for
application of fire sprinkler requirements, the floor area shall be
determined in accordance with the CBC definition for "Floor Area, Gross".
For Group R-3 occupancies portions of the structure not required to be
protected by the automatic sprinkler system do not need to be included
into the floor area calculation.
FLOWLINE is the ~Iowest continuous elevation on a rolled curb defined by
the path traced by a particle in a moving body of water at the bottom of the
rolled curb."
(b) SECTION 202, General Definitions, is hereby amended by modifying item
2 of the definition of HIGH-RISE BUILDING to read:
"High-rise structure" means every building of any type of construction or
occupancy having floors used for human occupancy located more than 55
feet above the lowest floor level having building access (see California
Building Code, Section 403.1.2), except buildings used as hospitals as
defined in Health and Safety Code Section 1250."
5131.03 Chapter 3 of the 2007 California Fire Code is hereby amended as follows:
(a) SECTION 305.5, is hereby amended as follows:
Ordinance No. 1345
Page 10
"305.5, Spark Arresters. All chimneys attached to any appliance or
fireplace that burns solid fuel shat! be equipped with an approved .spark
arrestor, the spark arrester shall meet all of the following requirements:
1. The net free area of the spark arrester shall not be less than four
times the net area of the outlet of the chimney.
2. The spark arrester screen shall have heat or corrosion resistance
equivalent to 12 gage wire, 19 gage galvanized wire or 24 gage
stainless steel.
3. Openings shall not permit the passage of spheres having a
diameter larger than '/z inch and shall not block the passage of
spheres having a diameter of less than 3/8 inch.
4. The spark arrester shall be accessible for cleaning and the screen
or chimney cap shall be removable to allow for cleaning of the
chimney flue."
(b) Chapter 3 is hereby amended by adding Section 316 to read:
"316 Development On Or Near Land Containing Or Emitting Toxic,
Combustible or Flammable Liquids, Gases or Vapors. The fire code
official may require the submittal for approval of geological studies,
evaluations, reports, remedial recommendations and/or similar
documentation from astate-licensed and department approved individual
or firm, on any parcel of land to be developed which:
1. Has, or is adjacent to, or within 1,000 feet (304 800 mm) of a parcel
of land that has an active, inactive, or abandoned oil or gas well
operation, petroleum or chemical refining facility, petroleum or
chemical storage, or
2. May contain or give off toxic, combustible or flammable liquids,
gases or vapors."
(c) Chapter 3 is hereby amended by adding Section 317 to read:
"317 Fuel Modification Requirements for New Construction. All new
buildings to be built or installed in areas containing combustible vegetation
shall comply with the following:
1. Preliminary fuel modification plans shall be submitted to and
approved by the fire code official concurrent with the submittal for
approval of any tentative map.
2. Final fuel modification plans shall be submitted to and approved by
the fire code official prior to the issuance of a grading permit.
3. The fuel modification plans shall meet the criteria set forth in the
Orange County Fire Authority Fuel Modification Plan Guidelines.
Ordinance No. 1345
Page 11
4. The fuel modification plan may be altered if conditions change. Any
alterations to the fuel modification shall be approved by the Fire
Code Official.
5. All elements of the fuel modification plan shall be maintained in
accordance with the approved plan and are subject to the
enforcement process outlined in the Fire Code."
(d) Chapter 3 is hereby amended by adding Section 318 to read:
"318 Clearance of brush or vegetative growth from structures.
A. General. Persons owning, leasing, controlling, operating or
maintaining buildings or structures in, upon or adjoining hazardous
fre areas, and persons owning, leasing or controlling land adjacent
to such buildings or structures, shall at all times:
1. Maintain an effective firebreak by removing and clearing
away flammable vegetation and combustible growth from
areas within 30 feet (9144 mm) of such buildings or
structures;
Exception: Single specimens of trees, ornamental shrubbery
or similar plants used as ground covers, provided that they
do not form a means of rapidly transmitting fire from the
native growth to any structure.
2. Maintain additional fire protection or firebreak by removing
brush, flammable vegetation and combustible growth located
from 30 feet to 100 feet (9144 mm to 30 480 mm) from such
buildings or structures, when required by the fire code official
because of extra hazardous conditions causing a firebreak of
only 30 feet (9144 mm) to be insufficient to provide
reasonable fire safety;
Exception:
Grass and other vegetation located more than 30 feet
(9144 mm} from buildings or structures and less than
18 inches (457 mm) in height above the ground need
not be removed where necessary to stabilize the soil
and prevent erosion.
3. Remove portions of trees which extend within 10 feet (3048
mm) of the outlet of a chimney;
4. Maintain trees adjacent to or overhanging a building free of
deadwood; and
Ordinance No. 1345
Page 12
5. Maintain the roof of a structure free of leaves, needles or
other dead vegetative growth.
B. Corrective Actions. The executive body is authorized to instruct the
fire code official to give notice to the owner of the property upon
which conditions regulated by Section 318 A exist to correct such
conditions. If the owner fails to correct such conditions, the
executive body is authorized to cause the same to be done and
make the expense of such correction a lien upon the property
where such condition exists."
(e) Chapter 3 is hereby amended by adding Section 319 to read:
"319 Clearance of brush or vegetation growth from roadways. The
fire code official is authorized to cause areas within 10 feet (3048 mm) on
each side of portions of highways and private streets which are improved,
designed or ordinarily used for vehicular traffic to be cleared of flammable
vegetation and other combustible growth. The fire code official is
authorized to enter upon private property to do so.
Exception: Single specimens of trees, ornamental shrubbery or cultivated
ground cover such as green grass, ivy, succulents or similar plants
used as ground covers, provided that they do not form a means of
readily transmitting fire."
(f) Chapter 3 is hereby amended by adding Section 320 to read:
"320 Unusual Circumstances. The fire code official may suspend
enforcement and require reasonable alternative measures designed to
advance the purposes of this chapter if he determines in any specific case
that any of the following conditions exist:
1. Difficult terrain.
2. Danger of erosion.
3. Presence of plants included in any state and federal resources
agencies, California Native Plant Society and county-approved list
of wildlife, plants, rare, endangered andlor threatened species.
4. Stands or groves of trees or heritage trees.
5. Other unusual circumstances that make strict compliance with the
clearance of vegetation provisions of Sections 15, 16 or 17 of this
appendix undesirable or impractical."
(g) Chapter 3 is hereby amended by adding Section 321 to read:
"321 Use of Equipment.
Ordinance No. 1345
Page 13
1. Except as otherwise provided in this section, no person shall use,
operate, or cause to be operated, in, upon or adjoining any
hazardous fire area any internal combustion engine which uses
hydrocarbon fuels, unless the engine is equipped with a spark
arrester as defined in Section 25.3 maintained in effective working
order, or the engine is constructed, equipped and maintained for
the prevention of fire pursuant to Section 25.3.
2. Spark arresters affixed to the exhaus# system of engines or
vehicles subject to this section shall not be placed or mounted in
such a manner as to allow flames or heat from the exhaust system
to ignite any flammable material.
3. A spark arrester is a device constructed of nonflammable material
specifically for the purpose of removing and retaining carbon and
other flammable particles over 0.0232 of an inch (0.58 mm} in size
from the exhaust flow of an internal combustion engine that uses
hydrocarbon fuels or which is qualified and rated by the United
States Forest Service.
4. Engines used to provide motor power for trucks, truck tractors,
buses, and passenger vehicles, except motorcycles, are not subject
to this section if the exhaust system is equipped with a muffler as
defined in the Vehicle Code of the State of California.
5. Turbocharged engines are not subject to this section if all
exhausted gases pass through the rotating turbine wheel, there is
no exhaust bypass to the atmosphere, and the turbocharger is in
effective mechanical condition."
(h) Chapter 3 is hereby amended by adding Section 322 to read:
"322 Restricted entry. The Fire Code Official shall determine and
publicly announce when hazardous fire areas shall be closed to entry and
when such areas shall again be opened to entry. Entry on and occupation
of hazardous fire areas, except public roadways, inhabited areas or
established trails and camp sites which have not been closed during such
time when the hazardous fire area is closed #o entry, is prohibited.
Exception:
1. Residents and owners of private property within hazardous
fire areas and their invitees and guests going to ar being
upon their lands.
2. Entry, in the course of duty, by peace or police officers, and
other duly authorized public officers, members of a fire
department and members of the United States Forest
Service."
(i) Chapter 3 is hereby amended by adding Section 323 to read:
Ordinance No. 1345
Page 14
"323 Trespassing on posted property.
A. General. When the fire code official determines that a specific area
within a hazardous fire area presents an exceptional and continuing
fire danger because of the density of natural growth, difficulty of
terrain, proximity to structures or accessibility to the public, such
areas shall be closed until changed conditions warrant termination
of closure. Such areas shall be posted as hereinafter provided.
B. Signs. Approved signs prohibiting entry by unauthorized persons
and referring to applicable fire code chapters shall be placed on
every closed area.
C. Trespassing. Entering and remaining within areas closed and
posted is prohibited.
Exception: Owners and occupiers of private or public property
within closed and posted areas, their guests or invitees, and
local, state and federal public officers and their authorized
agents acting in the course of duty.
(j) Chapter 3 is hereby amended by adding Section 324 to read:
"324 Explosives and blasting. Explosives shall not be possessed, kept,
s#ored, sold, offered for sale, given away, used, discharged, transported or
disposed of within hazardous fire areas except by permit from the fire
code official."
(k) Chapter 3 is hereby amended by adding Section 325 to read:
"325 Outdoor fires. Outdoor fires shall not be built, ignited or maintained
in or upon hazardous fire areas, except by permit from the fire code
official.
Exception: Outdoor fires within habited premises or designated campsites
where such fires are built in a permanent barbecue, portable barbecue,
outdoor fireplace, incinerator or grill and are a minimum of 30 feet (9144
mm) from agrass-, grain-, brush- orforest-covered area.
Permits shall incorporate such terms and conditions which will reasonably
safeguard public safety and property. Outdoor fires shall not be built,
ignited or maintained in or upon .hazardous fire areas under the following
conditions:
1. When high winds are blowing,
2. When a person age 17 or over is not present at all times to watch
and tend such fire, or
Ordinance No. 1345
Page 15
3. When public announcement is made that open burning is
prohibited.
Permanent barbecues, portable barbecues, outdoor fireplaces or grills
shall not be used for the disposal of rubbish, trash or combustible waste
material."
5131.04 Chapter 4, Emergency Planning and Preparedness, of the 2007 California
Fire Code is deleted without replacement.
5131.05 Chapter 5 of the 2007 California Fire Code is hereby amended as follows:
(a) SECTION 503.2.1, Dimensions, is hereby amended by adding the
following to the end of the first paragraph to read:
"Street widths are to be measured from top face of curb to top face of
curb, on streets with curb and gutter, and from flowline to flowline , on
streets with rolled curbs.
In areas defined as
• State Responsibility Area: Fire Hazard Severity Zones
• Local Responsibility Area: Wildland-Urban Interface Fire Area as
adopted by the local agencies
The minimum street width is 28 feet. When the road serves no more than
3 dwelling units and the road does not exceed 150 feet in length, the road
width may be 24 feet."
(b) SECTION 503.4, Obstruction of fire apparatus access roads, is hereby
amended by adding the following at the end of the first paragraph to read:
"Speed Bumps and speed humps shall be approved prior to installation."
(c) SECTION 503.6, Security gates, shall be amended by adding the
following language at the end of the first paragraph to read:
"Vehicle access gates or barriers shall be in accordance with the Orange
County Fire Authority Guidelines for Emergency access. All electrically
operated vehicle access gates shall be equipped with an automatic
opening device in addition to a key opening switch."
(d) SECTION 508.5.1, Where required, is hereby deleted and amended to
read:
"508.5.1 Where required. Where a por#ion of the facility or building
hereafter constructed or moved into or within the jurisdiction is more than
allowed in APPENDIX C from a hydrant on a fire apparatus access road,
Ordinance No. 1345
Page 16
as measured by an approved route around the exterior of the facility or
building, on-site fire hydrants and mains shall be provided where required
by the fire code official.
Exceptions:
For Group R-3 and Group U occupancies, the distance requirement shall
be 600 feet when fire sprinklers are installed throughout the
structure in accordance with NFPA 13D, 2002 Edition."
5131.06 CHAPTER 6 Building Services and Systems. Chapter 6 of the 2007 California
Fire Code is hereby amended as follows:
(a) SECTION 604.2.16.1.1 CFC, Standby power loads, is hereby deleted and
amended to read:
"604.2.'16.1.1 Standby power loads. The following loads are classified as
standby power loads:
1. Smoke control system.
2. Electrically driven fire pumps.
3. Standby power shall be provided for elevators in accordance with
Section 3003 of the California Building Code."
(b) SECTION 604.2.16.2.1 CFC, Emergency power loads, is hereby amended
as follows:
"604.2.1 6.2.1 Emergency power loads. The following loads are
classified as emergency power loads:
1. Emergency voice/alarm communication systems.
2. Fire alarm systems.
3. Automatic fire detection systems.
4. Elevator car lighting.
5. Means of egress lighting and exit sign illumination as required by
Chapter 10.
6. Ventilation and automatic fire detection equipment for smokeproof
enclosures."
(c) SECTION 606.8, Refrigerant Detector, is hereby deleted and amended to
read
"606.8 Refrigerant Detector. Machinery rooms shall contain a refrigerant
detector with an audible and visual alarm. The detector, or a sampling
tube that draws air to the detector, shall be located in an area where
refrigerant from a leak will concentrate. The alarm shall be actuated at a
value not greater than the corresponding TLV-TWA values shown in the
California Mechanical Code for the refrigerant classification. Detectors and
Ordinance No. 1345
Page 17
alarms shall be placed in approved locations. In addition, emergency
shutoff shall also be automatically activated when the concentration of
refrigerant vapor exceeds 25 percent of LFL."
(d) SECTION 606.10.1.2, Manual Operation, is hereby deleted and amended
to read
"606.1.2 Manual operation. When required by the fire code official,
automatic crossover valves shall be capable of manual operation. The
manual valves shall be located in an approved location immediately
outside of the machinery room, in a secure metal box and marked as
Emergency Controls."
(e) SECTION 608.1, Scope, is hereby deleted and amended to read:
"608.1 Scope. Stationary storage battery systems having an electrolyte
capacity of more than 50 gallons (189 L) for flooded lead acid, nickel
cadmium (Ni-Cd) and valve-regulated lead acid (VRLA}, or 1,000 pounds
(454 kg) for lithium-ion, used for facility standby power, emergency power,
uninterrupted power supplies, or indoor storage of electric carts/cars shall
comply with this section and Table 608.1."
5131.07 (Reserved
5131.08 (Reserved)
5131.09 Chapter 9 of the 2007 California Fire Code is hereby amended as follows:
(a} SECTION 903.2, Where required, is hereby deleted and amended as
follows:
"903.2 Where required. Approved automatic sprinkler systems in new
buildings and structures shall be provided in the locations described in this
section as follows:
1. New buildings. In addition to the requirements of sections 903.2.1
through 903.2.13, approved automatic sprinkler systems in new
buildings and structures shall be provided when the gross area of
the building exceeds 5,000 ft or more than two-story high.
Exception: Group R Detached one- two-family dwellings and
townhouses as required by section 903.2.7
Exception:
The elimination of sprinkler protection in the following areas are
subject to approval by Fire .Code Official. Spaces or areas in
telecommunications buildings used exclusively for
Ordinance No. 1345
Page 18
telecommunications equipment, associated electrical power
distribution equipment, batteries and standby engines, provided
those spaces or areas are equipped throughout with an automatic
fire alarm system and are separated from the remainder of the
building by fire barriers consisting of not less than 1-hour fire-
resistance-rated walls and 2-hour fire-resistance-rated floor/ ceiling
assemblies.
2. Alteration. When the floor area of the Alteration within any two-
year period exceeds 75% of area of the existing structure and the
alteration includes structural modifications other than seismic
upgrade.
3. Addition. Sprinkler protection shall be provided throughout the
entire building when:
4. Existing building less than 5,000 ft~. Where 20% or more is
added and the gross floor area exceeds 5,000 ft2.
5. Existing building equal or greater than 5,000 ftz. Where more
than 1,000 ft2 is added.
(b) SECTION 903.2.7, Group R, is hereby deleted and amended to read:
"903.2.7 Group R. An automatic sprinkler system installed in accordance
with Section 903.3 shall be provided throughout all buildings with a Group
R Occupancy.
An automatic sprinkler system shall be installed throughout any existing
building when the floor area of the Alteration within any two year period
exceeds 50% of area of the existing structure and the building area
exceeds 5,500 ft. When the cost of installing an approved automatic
sprinkler system exceeds 5% of the cost of the Alteration, with the
approval of the fire code official, the required automatic sprinkler system
may be omitted. .
Exceptions:
1. Detached buildings containing two or less dwelling units with less
than 5,500 ft2 (including attached U-occupancy).
2. Group R-3.1 occupancies not housing bedridden clients, not
housing nonambulatory clients above the second floor, and less
than 5,500 ftZ.
3. Pursuant to Health and Safety Code Section 13113 occupancies
housing ambulatory children only, none of whom are mentally ii{ or
mentally retarded, and building or portions thereof housing such
children are not more than two stories in height, and thereof
Ordinance No. 1345
Page 19
housing such children have an automatic fire alarm system
activated by approved smoke detectors.
4. Pursuant to Health and Safety Code Section 13143.6 occupancies
licensed for protective social care which house ambulatory clients
only, none of whom is a child (under the age of 18 years), or who is
elderly (65 years of age or over}."
(c) SECTION 903.3.'1.1.1, Exempt locations, is hereby amended by deletion
of exception 4.
(d) SECTION 903.4, Sprinkler system monitoring and alarms, exceptions, is
hereby deleted and amended to read:
"1. Automatic sprinkler systems protecting one- and two-family
dwellings protected by NFPA 13D sprinkler system with less than
100 sprinklers.
2. Limited area systems serving fewer thari 20 sprinklers.
3. Jockey pump control valves that are sealed or locked in the open
position.
4. Valves controlling the fuel supply to fire pump engines that are
sealed or locked in the open position.
5. Trim valves to pressure switches in dry, preaction and deluge
sprinkler systems that are sealed or locked in the open position."
(e) SECTION 905.4, Location of Class I standpipe hose connections, is
hereby amended by adding items 7 and 8 as follows:
"7. The centerline of the 2.5" outlet shall be no less than 18" above and
no more than 24" above the finished floor.
8. Every new building with any horizontal dimensions greater than 300
feet (91,440 mm) shall be provided with either access doors or a
2.5" outlets so that all portions of the building can be reached with
150 feet (45,720) of hose from an access door or hose outlet.
Required access doors shall be located in the exterior of the
building and shall be accessible without the use of a ladder. The
door dimensions shall be not less than 3 feet (914 mm) in width,
and not less than 6 feet 8 inches (2032 mm) in height."
(f) SECTION 907.2.12, High-rise buildings, is hereby deleted and amended
to read:
"907.2.12 High-rise buildings. High-rise buildings with a floor used for
human occupancy located more than 55 feet 16764 mm} above the lowest
level of fire department vehicle access shall be provided with an automatic
fire alarm system and an emergency voice/alarm communication system
in accordance with Section 907.2.12.2.
Ordinance No. 1345
Page 20
Exceptions:
1. Airport traffic control towers in accordance with Section
907.2.22 and Section 412 of the California Building Code.
2. Open parking garages in accordance with Section 406.3 of
the California Building Code.
3. Buildings with an occupancy in Group A-5 in accordance
with Section 303.1 of the California Building Code.
4. Low-hazard special occupancies in accordance with Section
503.1.1 of the California Building Code.
5. Buildings with an occupancy in Group H-1, H-2 or H-3 in
accordance with Section 415 of the California Building
Code."
(g) SECTION 907.2.12.1, Automatic fire detection, is hereby deleted and
amended as follows:
"907.2.12.1 Automatic fire detection. Smoke detectors shalt be provided
in accordance with this section. Smoke detectors shall be connected to an
automatic fire alarm system. The activation of any detector required by
this section shall operate the emergency voice/alarm communication
system. Duct smoke detectors shall operate as specified in Section
907.12. Smoke detectors shall be located as follows:
1. In each mechanical equipment, electrical, transformer, telephone
equipment or similar room which is not provided with sprinkler
protection, elevator machine rooms, and in elevator lobbies.
2. In the main return air and exhaust air plenum of each air-
conditioning system havin~q a capacity greater than 2,000 cubic feet
per minute (cfm) (0.94 m /s). Such detectors shall be located in a
serviceable area downstream of the last duct inlet.
3. At each connection to a vertical duct or riser serving two or more
stories from a return air duct or plenum of an air-conditioning
system. In Group R-1 and R-2 occupancies, a listed smoke
detector is allowed to be used in each return-air riser carrying not
more than 5,000 cfm (2.4 m3/s) and serving not more than 10 air-
inlet openings."
(h) SECTION 907.2.12.2, Emergency voice/alarm communication system, is
hereby deleted and amended to read.
"907.2.12.2 Emergency voicelalarm communication system. The
operation of any automatic fire detector, sprinkler water-flow device or
manual fire alarm box shall automatically sound an alert tone followed by
voice instructions giving approved information and directions for a general
or staged evacuation on a minimum of the alarming floor, the floor above
Ordinance No. 1345
Page 21
and the floor below, Duct smoke detectors shall operate as specified in
Section 907.12. Speakers shall be provided throughout the building by
paging zones. As a minimum, paging zones shall be provided as follows:
1. Elevator groups.
2. Exit stairways.
3. Each floor.
4. Areas of refuge as defined in Section 1002.1.
5. Dwelling Units in apartment houses.
6. Hotel guest rooms or suites.
Exception: In Group I-1 and I-2 occupancies, the alarm shall sound
in a constantly attended area and a general occupant notification
shall be broadcast over the overhead page."
(i) SECTION 907.9.3 High-rise buildings, is hereby deleted and amended to
read:
"907.9.3 High-rise building. In buildings with a floor used for human
occupancy that is located more than 55 feet (16764 mm) above the lowest
level of fire department vehicle access, a separate zone by floor shall be
provided for all of the following types of alarm-initiating devices where
provided:
1. Smoke detectors.
2. Sprinkler water-flow devices.
3. Manual fire alarm boxes.
4. Other approved types of automatic fire detection devices or
suppression systems."
(j) SECTION 907.12 Duct smoke detectors, is hereby deleted and amended
as follows:
"907.12 Duct smoke detectors. Duct smoke detectors shall be connected
to the building's fire alarm control unit when a fire alarm system is
provided. Activation of a duct smoke detector shall initiate a visible and
audible supervisory signal at a constantly attended location. Duct smoke
detectors shall not be used as a substitute for required open area
detection.
Exception:
In occupancies not required to be equipped with a fire alarm
system, actuation of a smoke detector shall activate a visible and
an audible signal in an approved location. Smoke detector trouble
conditions shall activate a visible or audible signal in an approved
location and shall be identified as air duct detector trouble."
Ordinance No. 1345
Page 22
(k) SECTION 910.3.2.2 Sprinklered buildings, is hereby deleted and
amended to read:
"9'10.3.2.2 Sprinklered buildings. Where installed in buildings equipped
with an approved automatic sprinkler system, smoke and heat vents shall
be designed to opera#e automatically by actuation of cheat-responsive
device rated at least 100° F above the operating temperature of the
sprinkler."
5131.10 (Reserved)
5131.1'1 Chapter 11 of the 2007 California Fire Code is hereby amended as
follows:
(a) SECTION 1102.1 is hereby amended by adding the following definitions:
"APPROACH-DEPARTURE PATH. The flight path of the helicopter as it
approaches or departs from the landing pad.
EMERGENCY HELICOPTER LANDING FACILITY (EHLF). A landing
area on the roof of a high rise building that is not intended to function as a
heliport or helistop but is capable of accommodating fire or medical
helicopters engaged in emergency operations. Federal Aviation
Administration (FAA) approval is not required for an EHLF.
SAFETY AREA. A defined area surrounding the landing pad which is free
of obstructions.
TAKEOFF AND LANDING AREA. The combination of the landing pad
centered within the surrounding safety area."
(b) Chapter 11 is hereby amended by adding Section 1108, Emergency
Helicopter Landing Facility (EHLF), to read:
"Section 1108
Emergency Helicopter Landing Facility (FREE)
1108.1 General. EHLF shall meet or exceed the following minimum
requirements and the California Building Code.
1108.2 Where required and rooftop landing pad. Every building of any
type of construction or occupancy having floors used for human
occupancy located more than 75 ft above the lowest level of the fire
department vehicle access shall have a rooftop emergency helicopter
landing facility (EHLF} in a location approved by the fire code official for
use by fire, police, and emergency medical helicopters only.
Ordinance No. 1345
Page 23
The landing pad shall be 50 ft. x 50 ft. or a 50 ft. diameter circle that is
pitched or sloped to provide drainage away from access points and
passenger holding areas at a slope of 0.5 percent to 2 percent. The
landing pad surface shall be constructed of approved non-combustible,
nonporous materials. It shall be capable of supporting a helicopter with a
maximum gross weight of 15,000 lbs. For structural design requirements,
see California Building Code.
1108.3 Approach-Departure Path. The emergency helicopter landing
facility shall have two approach-departure paths separated in plan from
each other by at least 90 degrees. No objects shall penetrate above the
approach-departure paths. The approach-departure path begins at the
edge of the landing pad, with the same width or diameter as the landing
pad and is a rising slope extending outward and upward at a ratio of eight
feet horizontal distance for every one foot of vertical height.
1108.4 Safety Area. The safety area is a horizontal plane level with the
landing pad surface and shall extend 25 ft in all directions from the edge of
the landing pad. No objects shall penetrate above the plane of the safety
area.
1108.5 Safety Net. (f the rooftop landing pad is elevated more than 30 in.
(2'-6") above the adjoining surfaces, a 6 ft in wide horizontal safety net
capable of supporting 25 psf shall be provided around the perimeter of
the landing pad. The inner edge of the safety net attached to the landing
pad shall be slightly dropped (greater than 5 in. but less than 18 in.) below
the pad elevation. The safety net shall slope upward but the outer safety
net edge shall not be above the elevation of the landing pad.
1108.6 Take-off and Landing Area. The takeoff and landing area shall be
free of obstructions and minimum 100 ft x 100 ft. or 100 ft. diameter.
1108.7 Wind Indicating Device. An approved wind indicating device
shall be provided but shall not extend into the safety area or the approach-
departure paths.
1108.8 Special Markings. The emergency helicopter landing facility shall
be marked as indicated in Figure 1108.8.1
1108.9 Means of Egress. The means of egress from the landing pad shall
comply with the provisions of Chapter 10 of the California Building Code.
Landing areas located on buildings or structures shall have two or more
means of egress. For landing areas less that 60 feet in length, or less than
2,000 square feet in area, the second means of egress may be a fire
escape or ladder leading to the floor below.
Ordinance No. 1345
Page 24
1108.10 Standpipe systems. The standpipe system shall be extended to
the roof level on which the EHLF is located. All portions of the EHLF area
shall be within 150 feet of a 2.5-inch outlet on a Class I or III standpipe.
1108.11 Fire extinguishers. A minimum of one portable fire extinguisher
having a minimum 80-B:C rating shall be provided and located near the
stairways or ramp to the landing pad. The fire extinguisher cabinets shall
not penetrate the approach-departure paths, or the safety area.
Installation, inspection, and maintenance of extinguishers shall be in
accordance with the CFC, Section 906.
1108.13 EHLF. Fueling, maintenance, repairs, or storage of helicopters
shall not be permitted.
Ordinance No. 1345
Page 25
Figure 1108.8.1 Helicopter Landing Pad Markings
50'
20' Inside Diameter Numbers:
~2' Line Widt 10' High
Red in Color 2' Line
Width
Red in Color
CP
Address Numbers: Touchdown ~.
5' High, 1' Line Width Pad Boundary
Black in Color 1' in Width
~---12345 Red in Color
5~
1. The preferred background is white or tan.
2. The circled, red numbers indicate the allowable weight that the facility is capable
of supporting in thousands of pounds. _
3. The numbers shall be oriented towards the preferred flight (typically facing the
prevailing wind}.
5131.12 (Reserved)
5131.13 (Reserved}
5131.14 (Reserved)
5131.15 (Reserved)
Ordinance No. 1345
Page 26
5131.16 (Reserved)
5131.17 Chapter 17 of the 2007 California Fire Code is hereby amended as
follows:
(a} SECTION 1701.1, Fumigation and Thermal Insecticidal Fogging, is hereby
deleted and amended to read:
"1701.1 Scope. Fumigation and thermal insecticidal fogging operations
shall be in accordance with Divisions fi and 7 of the Food and Agriculture
Code of the State of California."
(b) SECTION 1701.2, Permits, is hereby deleted and amended to read:
"1701,2 Notification of Fumigation. The chief shall be notified in writing
at least 24 hours before any building, structure or ship is to be closed in
connection with the use of toxic or flammable fumigants."
5131.18 (Reserved)
5131.19 Chapter 19 of the 2007 California Fire Code is hereby amended as
follows:
(a) SECTION 1901.2, Permit, is hereby amended by adding the following to
the end to read:
"Permits shall be required as .set forth in Appendix Chapter 1, Section
105.6. For Section 1908 see Miscellaneous Combustible Storage Permit."
(b} SECTION 1908.1, General, is hereby deleted and amended to read:
"1908.1 General. The storage and processing of more than 400 cubic
feet of wood chips, hogged materials, fines, compost and raw product
produced from yard waste, debris and recycling facilities shall comply with
this section."
(c} SECTION 1908.2, Storage site, is hereby deleted and amended to read:
"1908.2 Storage site. Storage sites shall be level and on solid ground or
other all-weather surface. Sites shall be thoroughly cleaned and approval
from fire code official obtained before transferring products to the site."
(d) SECTION 1908.3, Size of piles, is hereby deleted and amended to read:
"1908.3 Size of piles. Piles shall not exceed 15 feet in height, 50 feet in
width and 100 feet in length."
Ordinance No. 1345
Page 27
(e} SECTION 1908.7, Pile fire protection, is hereby amended by adding the
following to the end of the section to read:
"Oscillating sprinklers with a sufficient projectile reach are required to
maintain a 40% to 60% moisture content and wet down
burning/smoldering areas."
(f} SECTION 1908.9, Material handling equipment, is hereby amended by
adding the following sentence at the beginning of the section:
"All material handling equipment operated by an internal combustion
engine shall be provided and maintained with an approved spark arrester."
5131.20 (Reserved)
5131.21 (Reserved)
5131.22 (Reserved)
5131.23 Chapter 23 of the 2007 California Fire Code is hereby amended as
follows:
(a) SECTION 2308.3, Flue spaces, is hereby deleted and amended to read:
"2308.3 Flue spaces. Flue spaces shall be provided in accordance with
Table 2308.3. Required flue spaces shall be maintained. In double-row
racks apallet/commodity stop shall be provided along the longitudinal flue
space at each level. The stop shall be steel or other ferrous material '/4"
thick and in the mounted position shall extend a minimum of 4 inches above
the shelve or cross member, or other method approved by fire code official."
5131.24 (Reserved)
5131.25 (Reserved)
5131.26 (Reserved)
5131.27 Chapter 27 of the 2007 California Fire Code is hereby amended as
follows:
(a} SECTION 2701.5.2, Hazardous Materials Inventory Statement (HMIs), is
hereby amended by deleting the starting paragraph and amended to read:
"2701.5.2 Hazardous Materials Inventory Statement (HMIs). When
required by the fire code official, an Orange County Fire Authority
Ordinance No. 1345
Page 28
Chemical Classification Packet shall be completed and approved prior to
approval of plans, and/or the storage, use or handling of chemicals on the
premises. The HMiS shall include the following information:"
(b) Table 2703.1.1(1 }, Maximum Allowable Quantity Per Control Area, is
hereby amended by deleting Footnote K.
(c) SECTION 2703.1.1, Maximum allowable quantity per control area, is
hereby amended by adding section 2703.1.1.1 to read:
"2703.1.1.1 Extremely Hazardous Substances. No person shall use or
store any amount of extremely hazardous substances (EHS} in excess of
the disclosable amounts (see Health and Safety Code Section 25500 et
al) in a residential zoned or any residentially developed property."
(d) SECTION 2703.5, Hazard identification signs, is hereby amended by
modifying the NFPA standard as follows:
Section 2703.5 Hazard identification signs. Unless otherwise exempted by
the fire code official, visible hazard identification signs as specified in the
Orange County Fire Authority Signage Guidelines for the (remainder
unchanged)
5131.28 (Reserved)
5131.29 (Reserved)
5131.30 (Reserved)
5131.31 (Reserved)
5131.32 Chapter 32 of the 2007 California Fire Code is hereby amended as
follows:
(a) SECTION 3203.4.1, Identification signs, is hereby amended by modifying
the NFPA standard as follows:
Section 3203.4.1 identification signs. Visible hazard identification signs in
accordance with the .Orange County Fire Authority Signage Guidelines
shall be provided at entrances to buildings or areas in which cryogenic
fluids are stored, handled or used.
5131.33 Chapter 33 of the 2007 California Fire Code is hereby amended by adding
new sections 3309, 3310, 3311, and 3312 as follows:
(a} Section 3309 Firing. All fireworks displays shall be electrically fired.
Ordinance No. 1345
Page 29
(b) Section 3310 Seizure of Fireworks. The fire code official shall have the
authority to seize, take, remove and fireworks stored, sold, offered for
sale, used or handled in violation of the provisions of Title 19 CCR,
Chapter 6. Any seizure or removal pursuant to this section shall be in
compliance with all applicable statutory, constitutional, and decisional law.
(c) Section 3311 Displays. Fireworks displays shall be in accordance with the
Orange County Fire Authority Guidelines for Public Fireworks Displays,
with the regulations of the State Fire Marshal, and with the conditions of
the permit as approved by the fire code official.
(d} Section 3312 Retail Fireworks. The storage, use, sale, possession, and
handling of fireworks 1.4G (commonly referred to as Safe & Sane) and
fireworks 1.3G is prohibited.
Exception -Fireworks 1.4G and fireworks 1.3G may be part of an
electrically fired public display when permitted and conducted by a
licensed pyrotechnic operator.
5131.34 Chapter 34 of the 2007 California Fire Code is hereby amended as
follows:
(a) SECTION 3404.2.3.2, Label or placard, is hereby amended as follows:
Section 3404.2.3.2 Label or placard. Tanks more than 100 gallons in
capacity, which are permanently installed or mounted and used for the
storage of Class 1, II or IIIA liquids, shall bear a label and placard
identifying the material therein. Placards shall be in accordance with the
Orange County Fire Authority Signage Guidelines.
(b) SECTION 3406.5.1.7, Static protection, is hereby amended to add the
following paragraph at the end of the section:
Section 3406.5.1.7 Static Protection. Drag chains or similar devices on
tank vehicles shall not be used to meet the requirements of this section for
static protection.
5131.35 (Reserved)
5131.36 (Reserved)
5131.37 Chapter 37 of the 2007 California Fire Code is hereby amended as
follows:
Ordinance No. 1345
Page 30
(a) SECTION 3704.2.2.7. is hereby amended by deleting exception 1 without
substitution and renumbering 2 to 1 with noted modifications.
"1. Toxic gases -storage/use. Treatment systems are not required for
toxic gases supplied by cylinders or portable tanks not exceeding
1,700 pounds water capacity when the following are provided:
1.1 A gas detection system with a sensing interval not exceeding 5
minutes.
1.2 For storage, valve outlets are equipped with gas-tight outlet plugs or
caps.
1.3 For use, an approved automatic-closing fail safe valve" (remainder
unchanged)
5131.38 (Reserved)
5131.44 (Reserved)
5131.45 Chapter 45 REFERENCED STANDARDS of the 2007 California Fire Code
is hereby amended by revising Section 4501 Amendments to National
Fire Protection Association Standards, by clarifying that the standards and
amendments apply to ali systems in all occupancies, and the following:
(a) NFPA 13, 2002 Edition, Installation of Sprinkler Systems is hereby
amended as follows:
Section 6.8.5 of NFPA 13-2002 is hereby amended as follows:
"6.8.5 Fire department connections (FDC) shall be of an approved
type. The FDC shat! contain a minimum of two 2 '/~" inlets. The
location shall be approved and be no more than 150 feet from a
public hydrant. The size of piping and the number of inlets shall be
approved by the chief. If acceptable to the water authority, it may
be installed on the backflow assembly. Fire department inlet
connections shall be painted OSHA safety red. When the fire
sprinkler density design .requires 500 gpm (including inside hose
stream demand) or greater, or a standpipe system is included, four
2 '/z" inlets shall be provided. FDC may be located within 150 feet of
a private fire hydrant when approved by the chief."
Section 8.3.3.1 of NFPA 13-2002 is hereby revised as follows:
Ordinance No. 1345
Page 31
"8.3.3.1. When fire sprinkler systems are ins#alled in shell buildings
of undetermined use (Spec Buildings) other than warehouses (S
occupancies), fire sprinklers of the quick-response type shall be
used. Use is considered undetermined if a specific tenant/occupant
is not identified at the time the permit is issued. Sprinklers in light
hazard occupancies shall be one of the following:"
Section 8.6.5.2.1.4 of NFPA 13-2002 is hereby deleted without
replacement:
Section 8.15.1.1.2.4 of NFPA 13-2002 is hereby deleted in its entirety and
replaced as follows:
"8.15.1.1.2.4 Control valves shall be installed and positioned so that
they are operable not more than 7 feet above the finished floor."
Section 8.15.1.3.3 of NFPA 13-2002 is hereby added as follows:
"8.15.1.3.3 Post indicator valve(s) shall be located as specified in
NFPA 24."
Section 8.15.1.5 of NFPA 13-2002 is hereby revised as follows:
"8.15.1.5.1 Large private fire service main systems shall have
sectional indicating controlling valves at appropriate points when
the system serves more than four appurtenances in order to permit
sectionalizing the system in the event of a break or for making of
repairs or extensions. A hydrant or a single fire line service to a
building counts as one appurtenance."
Section 8.16.2.4.6 of NFPA 13-2002 is hereby revised as follows:
"8.16.2.4.6 Fire department connections shall be on the street side
of buildings and shall be located and arranged so that they are
immediately adjacent to the approved fire department access road
and that hose lines can be readily and conveniently attached to the
inlets without interference from nearby objects including buildings,
fence, posts, or other fire department connections."
Section 9.1.3.9 of NFPA 13-2002 is hereby revised as follows:
"9.1.3.9.1 Powder-driven studs prohibited., welding studs, and the
Ordinance No. 1345
Page 32
tools used for installing welding studs these devices shall be listed."
Section 9.1.3.9.2 of NFPA 13-2002 is hereby deleted without replacement:
Section 9.1.3.9.3 of NFPA 13-2002 is hereby deleted without replacement.
Section 9.1.3.9.4 of NFPA 13-2002 is hereby deleted without replacement.
Section 9.3.5.8.11 of NFPA 13-2002 is hereby revised as follows:
"9.3.5.8.11* Other material not specifically included in Table
9.3.5.8.9 (a), Table 9.3.5 ;8.9 (b), and Table 9.3.5.8.9 (c) shall be
permitted to be used if certified by a registered professional
engineer to support the loads determined in accordance with the
above criteria. Calculations shall be submitted where required by
the authority having jurisdiction."
FIGURE 9.3.9.5.1 of NFPA 13-2002 is hereby amended by deleting the
portion relating to lag screws and lag bolts in wood.
Section 9.3.7.8 of NFPA 13-2002 is hereby revised as follows:
"9.3.7.8 Powder-driven fasteners shall not be used to attach braces
to the building structure."
Section 11.1.3 of NFPA 13-2002 is hereby added as follows:
"11.1.3 When fire sprinkler systems are required in buildings of
undetermined use other than warehouses, they shall be designed
and installed to have a fire sprinkler density of not less than that
required for an Ordinary Hazard Group 2 use, with no reduction/s in
density or design area. Warehouse fire sprinkler systems shall be
designed to Figure 12.3.2.1.2 (d} curve "G".
Use is considered undetermined if a specific tenant/occupant is not
identified at the time the permit is issued. Where a subsequent
occupancy requires a system with greater capability, it shall be the
responsibility of the occupant to upgrade the system to the required
density for the new occupancy."
Section 11.2.3.1.1.1 of NFPA 13-2002 is hereby added as follows:
"11.2.3.1.1.1 The available water supply for fire sprinkler system
design shall be determined by one of the following methods, as
approved by the chief:
Ordinance No. 1345
Page 33
1. Subtract the project site elevation from the low water level for
the appropriate pressure zone and multiplying the result by
0.433;
2. Use a maximum of 40 psi, if available;
3. Utilize the Orange County Fire Authority water flow test
form/directions to document a flow test conducted by the local
water agency or a professional engineer licensed in the State of
California. The result shall be adjusted in accordance with the
graduated scaled found in the guideline."
Section 14.1.3 (43} of NFPA 13-2002 is hereby revised as follows:
"Section 14.1...3 (43}. Size and location of hydrants, showing the
size and number of outlets and if outlets are to be equipped with
independent gate valves. Whether hose houses and equipment are
to be provided, and by whom, shall be indicated. Static and residual
hydrants that were used in the flow tests shall be shown. Flow test
shall be completed within six months of the plan submittal to the
authority having jurisdiction."
(b) NFPA 13D, 2002 Edition, Installation of Sprinkler Systems in One-and
Two-Family Dwellings and Manufactured Homes is hereby amended as
follows:
Section 4.2.5 of NFPA 13D-2002 is hereby added as follows:
"4.2.5 Stock of Spare Sprinklers"
Section 4.2.5.1 of NFPA 13D-2002 is hereby added as follows:
"4.2.5.1. A supply of at least two sprinklers for each type shall be
maintained on the premises so that any sprinklers that have
operated or been damaged in any way can be promptly replaced."
Section 4.2.5.2 of NFPA 13D-2002 is hereby added as follows:
"4.2.5.2 The sprinklers shall correspond to the types and
temperature ratings of the sprinklers in the property."
Section 4.2.5.3 of NFPA 13D-2002 is hereby added as follows:
"4.2.5.3 The sprinkler shall be kept in a cabinet located where the
temperature to which they are subjected will at no time exceed 100
°F."
Ordinance No. 1345
Page 34
Section 4.2.5.4 of NFPA 13D-2002 is hereby added as follows:
"4.2.5.4 A special sprinkler wrench shall be provided and kept in the
cabinet to be used in the removal and installation of sprinklers.
One sprinkler wrench shall be provided for each type of sprinkler
installed."
Section 7.1.2 of NFPA 13D-2002 is hereby revised as follows:
"7.1.2 The separate system piping shall not have a separate control
valve unless supervised by a central station, proprietary, or remote
station alarm service."
SECTION 7.3 -Pressure Gauges of NFPA 13D-2002 is hereby deleted
and substituted with the following:
Section 7.3.1 is hereby deleted in its entirety and amended to read:
"7.3.1 At least one water pressure gauge shall be installed on the
riser assembly."
Section 7.6 of NFPA 13D-2002 is hereby deleted in its entirety and
replaced as follows:
"7.6 Exterior alarm indicating device shall be listed for outside
service and audible from the street from which the house is
addressed. Exterior audible devices shall be placed on the front or
side of the structure and the location subject to final approval by the
Chief.
Additional interior alarm devices shall be required to provide
audibility throughout the structure. Sound levels in all sleeping
areas with all intervening doors closed shall be a minimum of 15
DBA above the average ambient sound level but not less than 70
DBA.
Audible devices shall be powered from an uninterruptible circuit
(except for over-current protection) serving normally operated
appliances in the residence.
Exception No. 1: When an approved water flow monitoring system
is installed, interior audible devices may be powered through the
fire alarm control panel.
Ordinance No. 1345
Page 35
Exception No. 2: When smoke detectors specified under CBC
Section 310.9 are used to sound an alarm upon waterflow switch
activation."
Section 8.2.4 of NFPA 13D-2002 is hereby revised as follows:
"8.2.4 Sprinklers shall be positioned so that the response time and
discharge are not unduly affected by obstructions such as ceiling
slopes, beams, or light fixtures. In rooms or areas wi#h slopes,
multiple beams or construction features creating conditions where
sprinklers are obstructed, or the sprinkler head placement exceeds
parameters specified in the products listing, the plans shall be
reviewed and approved by the fire official."
Section 8.6.4 of NFPA 13D-2002 is hereby revised as follows:
"8.6.4 Sprinklers shall not be required in, open attached porches,
carports and similar open structures."
Section 8.6.4.1 of NFPA 13D-2002 is hereby added as follows:
"Section 8.6.4.1 Attached garages shall be protected with listed
quick response fire sprinklers, spaced to protect a maximum area
of 130 square feet {12.1 m2). The diameter of the main or cross-
main piping serving the lines in the garage shall be equal to the
largest diameter piping on any main or cross main within the
system."
Section 8.6.4.2 of NFPA 13D-2002 is hereby added as follows:
"8.6.4.2 All attics shall be protected with an intermediate
temperature quick response sprinkler which shall be located to
protect attic penetrations created by the access scuttles or
mechanical equipment."
{c) NFPA 13R, 2002 Edition, Installation of Sprinkler System in Residential
Occupancies up to and Including Four Stories in Height is hereby
amended as follows:
Section 6.6.8.1 of NFPA 13R-2002 is hereby revised as follows:
"6.6.8.1 A local water-flow alarms shall be provided on all sprinkler
systems and shall be connected to the building fire alarm or water-
flow monitoring system where provided. Group R occupancies
containing less than the number of stories, dwelling units or
occupant load specified in Section 100907.2.8of the 2007 California
Ordinance No. 1345
Page 36
Fire Code as requiring a fire alarm system shall be provided with a
minimum of one approved interior alarm device in each unit. Sound
levels in all sleeping areas shall be minimum of 15 DBA above the
average ambient sound or a minimum of 70 DBA with all
intervening doors closed. Alarms shall be audible within all other
living areas within each dwelling unit. When not connected to a fire
alarm or water-flow monitoring system, audible devices shall be
powered from an uninterruptible circuit (except for overcurrent
protection) serving normally operated appliances in the residence.
There shall also be a minimum of one exterior alarm indicating
device, listed for outside service and audible from the access
roadway that serves that building."
Section 6.7.1.5.3 of NFPA 13R-2002 is hereby revised as follows:
"6.7.1.5.3 Sprinklers shall be positioned so that the response time
and discharge are not unduly affected by obstructions such as
ceiling slope, beams, or light fixtures. In rooms or areas with
slopes, multiple beams or construction features creating conditions
where sprinklers are obstructed, or the sprinkler head placement
exceeds parameters specified in the products listing, the plans shall
be reviewed and approved by the fire official."
Section 6.8.5 of NFPA 13R-2002 is hereby revised as follows:
"Section 6.8.5 Sprinklers shall not be required in, penthouse
equipment rooms, elevator machine rooms, concealed spaces
dedicated exclusively to containing only dwelling unit ventilation
equipment, crawl spaces, floor/ceiling spaces, elevator shafts, and
other concealed spaces that are not used or intended for living
purposes or storage and do not contain fuel fired equipment."
Section 6.8.5.1 of NFPA 13R-2002 is hereby added as follows:
"6.8.5.1 Sprinklers shall not be required in attics that are not located
over dwelling units. When attics are separated by unit, each unit's
attic space may be protected per NFPA 13D Section 8.6.4.2. All
other attics shall be protected per NFPA 13."
(d) NFPA 14, 2003 Edition, Installation of Standpipe. and Hose Systems is
hereby amended as follows:
Section 6.3.5.4.1 of NFPA 14-2003 is hereby deleted in its entirety and
replaced as follows:
Ordinance No. 1345
Page 37
"6.3.5.4.1 The fire department connection shall have a minimum of
two 2-1/2", internal threaded (NHS) inlets. Additional inlets shall be
provided on a 250 GPM per inlet ratio to meet the system demand.
The inlets shall be provided with approved caps to protect the
system from entry of debris. The location of the FDC shall be
approved and be no more than 150 feet from a public hydrant. If
acceptable to the water authority, it may be installed on the
backflow assembly. Fire department inlet connections shall be
painted OSHA safety red."
Section 7.3.1 of NFPA 14-2003 is hereby is deleted in its entirety and
replaced as follows:
"7.3.1 Hose Connection Height Class I and III Standpipe hose
connections shall be unobstructed and shall be located not Less
than 18 inches or more than 24 inches above the finished floor.
Class ll Standpipe hose connections shall be unobstructed and
shall be located not less than 3 feet or more than 5 feet above the
finished floor."
(e) NFPA 24, 2002 Edition, Installation of Private Fire Service Mains and
Their Appurtenances is hereby amended as follows:
Section 4.2.1 of NFPA 24-2002 is hereby revised as follows:
"4.2.1. Installation work shall be performed by fully experienced and
responsible contractor. The contractor shall licensed in the state to
do to install fire service mains."
Section 4.2.2 of NFPA 24-2002 is hereby revised as follows:
"4.2.2 Installation or remodeling of private fire service mains shall
not begin until plans are approved and appropriate permits secured
from the authority having jurisdiction."
Section 5.5 of NFPA 24-2002 is hereby revised as follows:
"5.5 Connections larger than 2 inches to public water systems shall be
controlled by post indicator valves of an approved type and installed in
accordance with the requirements of Section 6.3. Where the water
authority has regulations regarding the connection of private fire
service mains, they shall apply. Where the water authority requires
back-flow protection the following methods or assemblies are
acceptable:
1. An above ground assembly approved by the water authority,
painted OSHA safety red, and with the valves locked in the open
Ordinance No. 1345
Page 38
position. Valves controlling more than 100 sprinkler heads shall be
monitored to an approved location.
2. A below ground assembly approved by the water authority and
located in an approved vault. The last valve on the assembly shall
be controlled by an approved post indicator device (see Figure A-
2.6 b}. The post indicator device shall be painted OSHA safety
red, be locked in the open position and if controlling more than 100
sprinkler heads monitored to an approved location."
Section 5.9.1.2 of NFPA 24-2002 is hereby revised as follows:
"5.9.1.2 Fire department connections shall be properly supported
and protected from mechanical injury."
Section 5.9.1.3 of NFPA 24-2002 is hereby revised as follows:
"5.9.1.3 The fire department connection shall be of an approved
type and contain a minimum of two 2 '/z" inlets. The location shall
be approved and be no more than 150 feet from a public fire
hydrant. The size of piping and the number of inlets shall be
approved by the chief. If acceptable to the water authority, it may
be installed on the backflow assembly. The supply pipe shall be
painted OSHA safety red."
Section 5.9.1.3.1 of NFPA 24-2002 is herby added as follows:
"5.9.1.3.1 When the sprinkler density design is 500 gpm (including
the interior hose stream demand) or greater, or a standpipe system
is included, four 2 '/z" inlets shall be provided."
Section 5.9.1.3.2 of NFPA 24-2002 is hereby added as follows:
"5.9.1.3.2 The fire department connection (FDC} may be located
within 150 feet of a private fire hydrant provided the FDC connects
down-stream of an aboveground sprinkler system check valve."
Section 5.9.5.1 of NFPA 24-2002 is hereby revised as follows:
"5.9.5.1 Fire department connections shall be on the street side of
building and so they are located immediately adjacent to the
approved fire department access road."
Section 6.3.3.2 of NFPA 24-2002 is hereby revised as follows:
"6.3.3.2 Where post indicator valves cannot be located in accordance
with 6.3.3.1, they shall be permitted to be located closer where
Ordinance No. 1345
Page 39
approved by the authority having jurisdiction, or:
1. Wall post indicating valves: shall be located on exterior walls
without building openings within 15 feet of the valve.
2. Valve room: When it is placed in valve rooms separated from
the building by a one-hour fire-barrier accessible only from the
exterior.
3. Exterior risers: They may be set in locations adjacent to
exterior walls without openings within 15 feet of the valve."
Section 6.5.1 of NFPA 24-2002 is hereby revised as follows:
"6.5.1 Large, private, fire service main systems shall have
indicating sectional controlling valves after four appurtenances to
permit sectionalizing the system in the event of a break or for
making of repairs or extensions. A hydrant or a single fire line
service to a building counts as one appurtenance."
Section 10.1.6.3 of NFPA 24-2002 is hereby added as follows:
"10.1.6.3 All ferrous pipe shall be coated and wrapped. Joints shall
be coated and wrapped after assembly. All fittings shall be
protected with a loose 8-mill polyethylene tube. The ends of the
tube shall be sealed with 2 inch wide tape approved for
underground use. Galvanizing does not meet the requirements of
this section."
Section 10.3.6.2 of NFPA 24-2002 is hereby revised as follows:
"10.3.6.2 All bolted joint accessories shall be cleaned and
thoroughly coated with asphalt or other corrosion-retarding
material, prior to poly-tube, and after installation."
Section 10.3.6.3 of NFPA 24-2002 is hereby added as follows:
"10.3.6.3 All bolts used in pipe joint assembly shall be stainless
steel."
Section 10.6.1.1 of NFPA 24-2002 is hereby added as follows:
"10.6.1.1 Pipe may run under a building to a maximum of 18
inches, measured from the interior of the exterior wall. The pipe
Ordinance No. 1345
Page 40
under the building or building foundation shall be stainless steel
and shall not contain mechanical joints or comply with 10.6.2."
Section 10.8.2.5 of NFPA 24-2002 is hereby added as follows:
"10.8.2.5 The trench shall be excavated for thrust blocks and
inspected prior to pour. Care shall be taken when forming and
pouring thrust blocks that fittings and joints are not buried in
concrete."
Section 10.9.1 of NFPA 24-2002 is hereby revised as follows:
"10.9.1 Backfill shall be tamped in layers and wetted or puddled
under and around pipe to prevent settlement or lateral movement.
Backfill shall consist of clean fill sand or pea gravel to a minimum fi"
below and to a minimum of 12" above the pipe."
5131.46 (Reserved)
5131.47 Chapter 47 of the 2007 California Fire Code is hereby amended as
follows:
(a) Section 4701.1 Scope is amended by adding the following statement #o
the end of the section:
"4701.1 Scope. (The entire section remains unchanged). The entire
chapter is effective January 01, 2008 regardless of delayed
implementation date adopted by the office of SFM or CBSC."
(b) Section 4702 definition of Wildland-Urban Interface Area is modified as
follows:
"Wildland-Urban Interface Area is a geographical area identified by the
state as a "Fire Hazard Severity Zone" in accordance with the public
resources code Sections 4201 through 4204 and Government Code
Sections 51175 through 51189, or other areas designated by the enforcing
agency to be at a significant risk from wildfires including Special Fire
Protection Areas and Very High Fire Hazard Severity Zones. See Section
86B for the applicable referenced Sections of the Government Code and
the Public Resources Code."
5131.A2, 5131 A3, 5131 A4, 5131 AA (Reserved)
5131.AB Appendix B of the 2007 California Fire Code is adopted with the following
modifications:
Ordinance No. 1345
Page 41
SECTION B105.2, Buildings other than one- and two- family dwellings, is hereby
amended a follows:
"A reduction in fire-flow of up to 50 percent, as approved by the Fire
Authority, is allowed when the building is provided with an. approved
automatic sprinkler system installed in accordance with Section 903.3.1.1 or
903.3.1.2. The resulting fire-flow shall not be less than 1,500 gallons per
minute for the prescribed duration as specified in Table B105.1."
5131.AC Appendix C of the 2007 California Fire Code is adopted with the following
modifications:
(a) Table C105.1, column 4 header is modified as follows:
"Maximum distance from any point on the street or fire department access
to a hydrant a.f,9' "
(b) Table C105.1, footnote f is added as follows:
"Fire hydrants shall be a minimum of 40 feet from building with exception of
detached one and two-family dwellings."
(c) Table C105.1, footnote g is added as follows:
"In .residential single family subdivisions, maximum hydrant spacing is
300feet. This spacing may be increased to 600 feet (182 880mm} if all the
homes and attached garages are protected with automatic fire sprinklers
systems with a minimum fireflow of 2,000 gpm."
SEVERABILITY OF PARTS OF THIS ORDINANCE AND THE ADOPTED CODES
If any section, subsection, sentence, clause, phrase or portion of this Ordinance is for any
reason held out to be invalid or unconstitutional by the decision of any court of competent
jurisdiction, such decision shall not affect the validity of the remaining portions of this
ordinance. The City Council of the City of Tustin hereby declares that it would have
adopted this ordinance and each section, subsection, sentence, clause, phrase or portion
thereof irrespective of .the fact that any one or more sections, subsection, sentence clause,
phrases or portions be declared valid or unconstitutionally.
Ordinance No. 1345
Page 42
PASSED AND ADOPTED at a regular meeting of a City Council of the City of Tustin,
held on the 20th day of November, 2007. ;
LOU BONE
Mayor
PAMELA STOKER
City Clerk
STATE OF CALIFORNIA )
COUNTY OF ORANGE } SS
CITY OF TUSTIN )
CERTIFICATION FOR ORDINANCE NO. 1345
PAMELA STOKER, City Clerk and ex-officio Clerk of the City Council of the City of Tustin,
California, does hereby certify that the whole number of the members of the City Council of
the City of Tustin is 5; that the above and foregoing Ordinance No. 1345 was duly and
regularly introduced at a regular meeting of the Tustin City Council, held on the 20st day
of November, 2007 and was given its second reading, passed and adopted at a regular
meeting of the City Council .held on the 20 day of November, 2007 by the following vote:
COUNCILMEMBER AYES: Bone, Amante, Davert, Kawashima, Palmer (5)
COUNCILMEMBER NOES: None (0)
COUNCILMEMBER ABSTAINED: None (0)
COUNCILMEMBER ABSENT: None (0)
Pamela Stoker, Clerk