HomeMy WebLinkAboutPCM 02062024LA Testing
5431 Industrial Drive Huntington Beach, CA 92649
Tel/Fax: (714) 828-4999 / (714) 828-4944
http://www.LATesting.com / hblab@latesting.com
LA Testing Order:332402060
Customer ID:CTEH99
Customer PO:
Project ID:PROJ-032229
Attention:Noah Ambos Phone:(501) 454-1622
CTEH Center for Toxicology & Env. Health Fax:(501) 614-2835
5120 North Shore Drive Received Date:02/07/2024 10:00 AM
North Little Rock, AR 72118 Analysis Date:02/07/2024
Collected Date:02/06/2024
Project:PROJ-032229 (PROJ-032229)
Test Report: Fiber Count by Phase Contrast Microscopy (PCM), NIOSH 7400 Method - A Rules,
Revision 3, Issue 3, 6/14/2019
Sample Location Sample Date Volume (L)Fibers Fields
LOD
(fib/cc)Fibers/mm²Fibers/cc Notes
TUCA0206AS001A 02/06/2024 968.7 <5.5 100 0.0028 <7.01 <0.0028
332402060-0001
TUCA0206AS002A 02/06/2024 1086.5 <5.5 100 0.0025 <7.01 <0.0025
332402060-0002
TUCA0206AS003A 02/06/2024 1032.9 <5.5 100 0.0026 <7.01 <0.0026
332402060-0003
TUCA0206AS004A 02/06/2024 955.7 <5.5 100 0.0028 <7.01 <0.0028
332402060-0004
TUCA0206AS005A 02/06/2024 1042 <5.5 100 0.0026 <7.01 <0.0026
332402060-0005
TUCA0206AS006A 02/06/2024 1061.3 <5.5 100 0.0025 <7.01 <0.0025
332402060-0006
TUCA0206AS007A 02/06/2024 1100.2 <5.5 100 0.0024 <7.01 <0.0024
332402060-0007
TUCA0206AS008A 02/06/2024 1095.9 <5.5 100 0.0025 <7.01 <0.0025
332402060-0008
TUCA0206AS009A 02/06/2024 1007.4 <5.5 100 0.0027 <7.01 <0.0027
332402060-0009
TUCA0206AS010A 02/06/2024 1016.1 <5.5 100 0.0027 <7.01 <0.0027
332402060-0010
TUCA0206AS013A 02/06/2024 1076.8 <5.5 100 0.0025 <7.01 <0.0025
332402060-0011
TUCA0206AS014A 02/06/2024 847.8 <5.5 100 0.0032 <7.01 <0.0032
332402060-0012
TUCA0206AS015A 02/06/2024 993.1 <5.5 100 0.0027 <7.01 <0.0027
332402060-0013
TUCA0206AS017A 02/06/2024 927.3 <5.5 100 0.0029 <7.01 <0.0029
332402060-0014
TUCA0206AS018A 02/06/2024 908.8 <5.5 100 0.0030 <7.01 <0.0030
332402060-0015
TUCA0206AS019A 02/06/2024 1013.2 <5.5 100 0.0027 <7.01 <0.0027
332402060-0016
TUCA0206AS021A 02/06/2024 857.4 <5.5 100 0.0031 <7.01 <0.0031
332402060-0017
LA Testing maintains liability limited to cost of analysis. Interpretation and use of test results are the responsibility of the client. This report relates only to the samples reported above, and may not be reproduced, except
in full, without written approval by LA Testing. LA Testing bears no responsibility for sample collection activities or analytical method limitations. The report reflects the samples as received. Results are generated from the
field sampling data (sampling volumes and areas, locations, etc.) provided by the client on the Chain of Custody. Samples are within quality control criteria and met method specifications unless otherwise noted. Limit of
detection is 7 fibers/mm². Fiber counts outside the recommended fiber density range of the method (100-1300 f/mm²) have greater than optimal variability and are probably biased. Field blank results, when available, are
used to blank correct results. NIOSH 7400 requires field blanks be submitted at a rate of 10%, with a minimum of 2 per set. Measurement of uncertainty available upon request. The results in this report meet all
requirements of the NELAC standards unless otherwise noted. Intra-laboratory Sr values: 5-20 fibers = 0.25, 21-50 fibers = 0.22, 51-100 fibers = 0.18. Inter-laboratory Sr values (Average of EMSL round robin data) =
0.33.
Samples analyzed by LA Testing Huntington Beach, CA AIHA LAP, LLC-IHLAP Accredited #101650
Initial report from: 02/07/2024 03:42 PM
Printed: 02/07/2024 03:42 PM ASB_PCM_NoSig_0003_0001 Page 1 of 2
LA Testing
5431 Industrial Drive Huntington Beach, CA 92649
Tel/Fax: (714) 828-4999 / (714) 828-4944
http://www.LATesting.com / hblab@latesting.com
LA Testing Order:332402060
Customer ID:CTEH99
Customer PO:
Project ID:PROJ-032229
Attention:Noah Ambos Phone:(501) 454-1622
CTEH Center for Toxicology & Env. Health Fax:(501) 614-2835
5120 North Shore Drive Received Date:02/07/2024 10:00 AM
North Little Rock, AR 72118 Analysis Date:02/07/2024
Collected Date:02/06/2024
Project:PROJ-032229 (PROJ-032229)
Test Report: Fiber Count by Phase Contrast Microscopy (PCM), NIOSH 7400 Method - A Rules,
Revision 3, Issue 3, 6/14/2019
Sample Location Sample Date Volume (L)Fibers Fields
LOD
(fib/cc)Fibers/mm²Fibers/cc Notes
TUCA0206ASFB001A 02/06/2024 <5.5 100 <7.01 Field Blank
332402060-0018
TUCA0206AS001B 02/06/2024 1041.9 <5.5 100 0.0026 <7.01 <0.0026
332402060-0019
TUCA0206AS002B 02/06/2024 1070.6 <5.5 100 0.0025 <7.01 <0.0025
332402060-0020
TUCA0206AS003B 02/06/2024 1093.9 <5.5 100 0.0025 <7.01 <0.0025
332402060-0021
TUCA0206AS004B 02/06/2024 1049.1 <5.5 100 0.0026 <7.01 <0.0026
332402060-0022
TUCA0206AS005B 02/06/2024 1057.4 <5.5 100 0.0025 <7.01 <0.0025
332402060-0023
TUCA0206AS006B 02/06/2024 951.8 <5.5 100 0.0028 <7.01 <0.0028
332402060-0024
TUCA0206AS007B 02/06/2024 1052.6 <5.5 100 0.0026 <7.01 <0.0026
332402060-0025
TUCA0206AS008B 02/06/2024 1057.8 <5.5 100 0.0025 <7.01 <0.0025
332402060-0026
TUCA0206AS009B 02/06/2024 1075.3 <5.5 100 0.0025 <7.01 <0.0025
332402060-0027
TUCA0206AS010B 02/06/2024 1047.6 <5.5 100 0.0026 <7.01 <0.0026
332402060-0028
TUCA0206ASFB001B 02/06/2024 <5.5 100 <7.01 Field Blank
332402060-0029
The results reported have been blank corrected as applicable.
Michael Chapman, Laboratory Manager
or other Approved Signatory
Analyst(s):
Christopher Miranda PCM 29
LA Testing maintains liability limited to cost of analysis. Interpretation and use of test results are the responsibility of the client. This report relates only to the samples reported above, and may not be reproduced, except
in full, without written approval by LA Testing. LA Testing bears no responsibility for sample collection activities or analytical method limitations. The report reflects the samples as received. Results are generated from the
field sampling data (sampling volumes and areas, locations, etc.) provided by the client on the Chain of Custody. Samples are within quality control criteria and met method specifications unless otherwise noted. Limit of
detection is 7 fibers/mm². Fiber counts outside the recommended fiber density range of the method (100-1300 f/mm²) have greater than optimal variability and are probably biased. Field blank results, when available, are
used to blank correct results. NIOSH 7400 requires field blanks be submitted at a rate of 10%, with a minimum of 2 per set. Measurement of uncertainty available upon request. The results in this report meet all
requirements of the NELAC standards unless otherwise noted. Intra-laboratory Sr values: 5-20 fibers = 0.25, 21-50 fibers = 0.22, 51-100 fibers = 0.18. Inter-laboratory Sr values (Average of EMSL round robin data) =
0.33.
Samples analyzed by LA Testing Huntington Beach, CA AIHA LAP, LLC-IHLAP Accredited #101650
Initial report from: 02/07/2024 03:42 PM
Printed: 02/07/2024 03:42 PM ASB_PCM_NoSig_0003_0001 Page 2 of 2