HomeMy WebLinkAboutPCM 04062024LA Testing
5431 Industrial Drive Huntington Beach, CA 92649
Tel/Fax: (714) 828-4999 / (714) 828-4944
http://www.LATesting.com / hblab@latesting.com
LA Testing Order:332406372
Customer ID:CTEH99
Customer PO:
Project ID:PROJ-032229
Attention:Noah Ambos Phone:(501) 454-1622
CTEH Center for Toxicology & Env. Health Fax:(501) 614-2835
5120 North Shore Drive Received Date:04/08/2024 10:35 AM
North Little Rock, AR 72118 Analysis Date:04/08/2024
Collected Date:04/06/2024
Project:PROJ-032229 (PROJ-032229)
Test Report: Fiber Count by Phase Contrast Microscopy (PCM), NIOSH 7400 Method - A Rules,
Revision 3, Issue 3, 6/14/2019
Sample Location Sample Date Volume (L)Fibers Fields
LOD
(fib/cc)Fibers/mm²Fibers/cc Notes
TUCA0406AS001A 04/06/2024 1083 <5.5 100 0.0025 <7.01 <0.0025
332406372-0001
TUCA0406AS002A 04/06/2024 1017.2 <5.5 100 0.0026 <7.01 <0.0026
332406372-0002
TUCA0406AS003A 04/06/2024 1082.4 <5.5 100 0.0025 <7.01 <0.0025
332406372-0003
TUCA0406AS004A 04/06/2024 907 <5.5 100 0.0030 <7.01 <0.0030
332406372-0004
TUCA0406AS005A 04/06/2024 1019.6 <5.5 100 0.0026 <7.01 <0.0026
332406372-0005
TUCA0406AS006A 04/06/2024 1073.1 <5.5 100 0.0025 <7.01 <0.0025
332406372-0006
TUCA0406AS007A 04/06/2024 1078.9 <5.5 100 0.0025 <7.01 <0.0025
332406372-0007
TUCA0406AS008A 04/06/2024 1078.2 <5.5 100 0.0025 <7.01 <0.0025
332406372-0008
TUCA0406AS009A 04/06/2024 1069.2 <5.5 100 0.0025 <7.01 <0.0025
332406372-0009
TUCA0406AS010A 04/06/2024 996.9 <5.5 100 0.0027 <7.01 <0.0027
332406372-0010
TUCA0406AS013A 04/06/2024 1017.4 <5.5 100 0.0026 <7.01 <0.0026
332406372-0011
TUCA0406AS014A 04/06/2024 704.9 <5.5 100 0.0038 <7.01 <0.0038
332406372-0012
TUCA0406AS015A 04/06/2024 813.2 <5.5 100 0.0033 <7.01 <0.0033
332406372-0013
TUCA0406AS017A 04/06/2024 837.7 <5.5 100 0.0032 <7.01 <0.0032
332406372-0014
TUCA0406AS018A 04/06/2024 979.7 <5.5 100 0.0028 <7.01 <0.0028
332406372-0015
TUCA0406AS021A 04/06/2024 1103.2 <5.5 100 0.0024 <7.01 <0.0024
332406372-0016
TUCA0406ASFB001A 04/06/2024 <5.5 100 <7.01 Field Blank
LA Testing maintains liability limited to cost of analysis. Interpretation and use of test results are the responsibility of the client. This report relates only to the samples reported above, and may not be reproduced, except
in full, without written approval by LA Testing. LA Testing bears no responsibility for sample collection activities or analytical method limitations. The report reflects the samples as received. Results are generated from the
field sampling data (sampling volumes and areas, locations, etc.) provided by the client on the Chain of Custody. Samples are within quality control criteria and met method specifications unless otherwise noted. Limit of
detection is 7 fibers/mm². Fiber counts outside the recommended fiber density range of the method (100-1300 f/mm²) have greater than optimal variability and are probably biased. Field blank results, when available, are
used to blank correct results. NIOSH 7400 requires field blanks be submitted at a rate of 10%, with a minimum of 2 per set. Measurement of uncertainty available upon request. The results in this report meet all
requirements of the NELAC standards unless otherwise noted. Intra-laboratory Sr values: 5-20 fibers = 0.25, 21-50 fibers = 0.22, 51-100 fibers = 0.18. Inter-laboratory Sr values (Average of EMSL round robin data) =
0.33.
Samples analyzed by LA Testing Huntington Beach, CA AIHA LAP, LLC-IHLAP Accredited #101650
Initial report from: 04/08/2024 02:39 PM
Printed: 04/08/2024 02:39 PM ASB_PCM_NoSig_0003_0001 Page 1 of 2
LA Testing
5431 Industrial Drive Huntington Beach, CA 92649
Tel/Fax: (714) 828-4999 / (714) 828-4944
http://www.LATesting.com / hblab@latesting.com
LA Testing Order:332406372
Customer ID:CTEH99
Customer PO:
Project ID:PROJ-032229
Attention:Noah Ambos Phone:(501) 454-1622
CTEH Center for Toxicology & Env. Health Fax:(501) 614-2835
5120 North Shore Drive Received Date:04/08/2024 10:35 AM
North Little Rock, AR 72118 Analysis Date:04/08/2024
Collected Date:04/06/2024
Project:PROJ-032229 (PROJ-032229)
Test Report: Fiber Count by Phase Contrast Microscopy (PCM), NIOSH 7400 Method - A Rules,
Revision 3, Issue 3, 6/14/2019
Sample Location Sample Date Volume (L)Fibers Fields
LOD
(fib/cc)Fibers/mm²Fibers/cc Notes
332406372-0017
TUCA0406AS001B 04/06/2024 1015.7 <5.5 100 0.0027 <7.01 <0.0027
332406372-0018
TUCA0406AS002B 04/06/2024 1022.1 <5.5 100 0.0026 <7.01 <0.0026
332406372-0019
TUCA0406AS003B 04/06/2024 1091.9 <5.5 100 0.0025 <7.01 <0.0025
332406372-0020
TUCA0406AS004B 04/06/2024 1067.2 <5.5 100 0.0025 <7.01 <0.0025
332406372-0021
TUCA0406AS005B 04/06/2024 1034.5 <5.5 100 0.0026 <7.01 <0.0026
332406372-0022
TUCA0406AS006B 04/06/2024 1009 <5.5 100 0.0027 <7.01 <0.0027
332406372-0023
TUCA0406AS007B 04/06/2024 987.9 <5.5 100 0.0027 <7.01 <0.0027
332406372-0024
TUCA0406AS008B 04/06/2024 1043.2 <5.5 100 0.0026 <7.01 <0.0026
332406372-0025
TUCA0406AS009B 04/06/2024 1085.4 <5.5 100 0.0025 <7.01 <0.0025
332406372-0026
TUCA0406AS010B 04/06/2024 1053.9 <5.5 100 0.0026 <7.01 <0.0026
332406372-0027
TUCA0406ASFB001B 04/06/2024 <5.5 100 <7.01 Field Blank
332406372-0028
The results reported have been blank corrected as applicable.
Michael Chapman, Laboratory Manager
or other Approved Signatory
Analyst(s):
Kaylin Luciani PCM 28
LA Testing maintains liability limited to cost of analysis. Interpretation and use of test results are the responsibility of the client. This report relates only to the samples reported above, and may not be reproduced, except
in full, without written approval by LA Testing. LA Testing bears no responsibility for sample collection activities or analytical method limitations. The report reflects the samples as received. Results are generated from the
field sampling data (sampling volumes and areas, locations, etc.) provided by the client on the Chain of Custody. Samples are within quality control criteria and met method specifications unless otherwise noted. Limit of
detection is 7 fibers/mm². Fiber counts outside the recommended fiber density range of the method (100-1300 f/mm²) have greater than optimal variability and are probably biased. Field blank results, when available, are
used to blank correct results. NIOSH 7400 requires field blanks be submitted at a rate of 10%, with a minimum of 2 per set. Measurement of uncertainty available upon request. The results in this report meet all
requirements of the NELAC standards unless otherwise noted. Intra-laboratory Sr values: 5-20 fibers = 0.25, 21-50 fibers = 0.22, 51-100 fibers = 0.18. Inter-laboratory Sr values (Average of EMSL round robin data) =
0.33.
Samples analyzed by LA Testing Huntington Beach, CA AIHA LAP, LLC-IHLAP Accredited #101650
Initial report from: 04/08/2024 02:39 PM
Printed: 04/08/2024 02:39 PM ASB_PCM_NoSig_0003_0001 Page 2 of 2